ℹ️ About This Calculator
Selecting the correct cable size is one of the most critical tasks in electrical design. An undersized cable overheats and becomes a fire hazard; an oversized cable wastes material cost. IS 732 (Code of Practice for Electrical Wiring Installations) requires that every cable be sized to satisfy two simultaneous criteria: current-carrying capacity and voltage drop.
IS 732 current capacity tables (Table 4, 5 etc.) give the rated current for different installation methods - clipped direct to surface, in conduit, or in trunking. Each installation method has a derating factor. For example, a 4mm² copper cable clipped direct carries 32A, but in a conduit (grouped with other cables) this may derate to 20A. Always apply the correct derating factors for ambient temperature, grouping, and soil thermal resistivity for buried cables.
📐 Cable Sizing Method (IS 732)
IS 732 / BS 7671
Step 1 - Full Load Current: 3-Phase: I = P / (√3 × V × PF) 1-Phase: I = P / (V × PF) Step 2 - Select cable ≥ I (from IS 732 current capacity tables, derated for installation) Step 3 - Check voltage drop: Vd = (2 × L × I × ρ) / A [single phase] Vd = (√3 × L × I × ρ) / A [three phase] Require: Vd/V ≤ 3% Step 4 - If VD > 3%, select next larger cable size and recheck.
🧮 Worked Example
A 3-phase 15kW motor (PF 0.85, 415V) runs through a 40m cable. Full load current: I = 15,000 / (1.732 × 415 × 0.85) ≈ 24.6A.
From IS 732 tables, a 6mm² copper cable (clipped direct) carries 36A - well above 24.6A. Checking voltage drop: Vd = (1.732 × 40 × 24.6 × 0.0172) / 6 ≈ 2.93V (0.71%), comfortably within the 3% limit. If the run were 100m instead, Vd would rise to 7.3V (1.76%) - still compliant, but a 10mm² cable would bring it down to about 4.4V (1.06%) with margin for future load growth.
📊 Cable Sizing Reference (IS 732 / IEC 60364)
How a cable size is selected: under IS 732 (and IEC 60364) the conductor must pass two independent checks — it must carry the design current after derating, and it must keep voltage drop within the 3% limit over the cable run. The larger of the two sizes governs; this calculator applies both automatically.
Indicative Current-Carrying Capacity — PVC-Insulated Copper (IS 732)
| Conductor (mm²) | Capacity (A) | Typical use |
|---|---|---|
| 1.5 | 15 | Lighting circuits |
| 2.5 | 20 | Socket / small power |
| 4 | 27 | Power circuits, small AC |
| 6 | 34 | Geyser, larger AC |
| 10 | 46 | Sub-mains, small motors |
| 16 | 61 | Sub-mains, motor feeders |
| 25 | 80 | Distribution feeders |
| 35 | 99 | Feeders |
| 50 | 119 | Main feeders |
| 70 | 151 | Main feeders |
| 95 | 182 | Incomers, large feeders |
Indicative values for PVC-insulated copper conductors, two to three loaded cores in conduit at 40 °C ambient. Ratings vary with installation method and manufacturer — always confirm against the cable maker's data sheet and the actual reference method before finalising.
Derating Factors (apply before comparing with design current)
| Ambient temp (°C) | Factor (PVC) | Grouped circuits | Factor |
|---|---|---|---|
| 30 | 1.15 | 1 circuit | 1.00 |
| 35 | 1.08 | 2 circuits | 0.80 |
| 40 (base) | 1.00 | 3 circuits | 0.70 |
| 45 | 0.91 | 4 circuits | 0.65 |
| 50 | 0.82 | 6 circuits | 0.57 |
Effective capacity = tabulated rating × ambient factor × grouping factor. In much of India the design ambient is 40–45 °C, so a derating below the 40 °C base is common and must not be ignored — it is a frequent cause of under-sized feeders.
Copper vs Aluminium
Aluminium has about 1.6× the resistivity of copper, so an aluminium conductor must be roughly one to two sizes larger for the same current and voltage drop. Aluminium is lighter and cheaper for large feeders and risers; copper is preferred for final circuits, control wiring and where terminations and space are tight. This calculator handles both — switch the material to compare.
❓ Frequently Asked Questions
🔗 Related Calculators
🧮 110 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/NBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →