ℹ About This Calculator
A cooling coil pulls moisture out of the air, and that condensate has to leave the drain pan reliably. Undersized or flat drain lines back water into the pan, which overflows into ceilings and grows microbial slime. This calculator gives the condensate flow rate from cooling capacity, the drain pipe size per IMC Table 307.2.2, and the fall required at your chosen slope.
Condensate rate is driven by latent load, not just tonnage - a humid coastal AHU can shed three times the water of the same unit in a dry climate, which is why the humidity factor matters. Beyond size and slope, two things cause most drain failures: no P-trap (or the wrong trap depth) on a draw-through unit, and no air break or vent, which makes the line airlock and drain in slugs. Always trap the pan outlet, slope continuously at 1% or more, and provide a cleanout - condensate lines block with biofilm more often than any other pipe in the building.
Condensate Flow & Drain Size (ASHRAE / IMC 307)
ASHRAE / IMC 307
Condensate flow: Q (L/hr) ≈ TR × humidity factor × 1.2 humidity factor: dry 0.5 | moderate 1.0 | humid/coastal 1.5 Drain pipe size (IMC Table 307.2.2, by equipment capacity): up to 3 TR -> 20 mm (3/4") 4 - 20 TR -> 25 mm (1") 21 - 90 TR -> 32 mm (1-1/4") 91 - 125 TR -> 40 mm (1-1/2") 126- 250 TR -> 50 mm (2") Slope: Minimum 1% (approx 10 mm fall per metre) Fall per 10 m = slope% × 100 mm
Condensate Drain Sizing Reference (IMC 307 / ASHRAE)
Drain size comes from cooling capacity, not condensate flow. IMC Table 307.2.2 fixes the minimum pipe diameter by equipment tonnage, while the condensate flow rate (driven by the latent load and humidity) tells you how much water the trap and slope must actually carry.
Minimum Drain Size by Cooling Capacity (IMC Table 307.2.2)
| Equipment capacity | Min. drain (metric) | Min. drain (inch) |
|---|---|---|
| Up to 3 TR | 20 mm | 3/4" |
| 4 – 20 TR | 25 mm | 1" |
| 21 – 90 TR | 32 mm | 1-1/4" |
| 91 – 125 TR | 40 mm | 1-1/2" |
| 126 – 250 TR | 50 mm | 2" |
So a typical 5 TR split or AHU needs a 25 mm (1") drain, a 2 TR unit needs 20 mm (3/4"). Never reduce below the drain-pan outlet size, and always round up at a band boundary.
Condensate Flow — Humidity Factor
| Climate / coil condition | Factor | Approx. flow |
|---|---|---|
| Dry / low RH (inland winter) | 0.5 | ≈ 0.6 L/hr per TR |
| Moderate | 1.0 | ≈ 1.2 L/hr per TR |
| Humid / coastal (monsoon) | 1.5 | ≈ 1.8 L/hr per TR |
Flow ≈ TR × factor × 1.2 L/hr. A 10 TR AHU on a humid coastal day can shed ~18 L/hr — the same unit inland in winter, barely 6 L/hr.
Slope & Trap
Slope the line continuously at ≥ 1% (10 mm fall per metre; 1/8" per foot). Every draw-through coil (pan under negative pressure) needs a P-trap deep enough to hold against the fan static — trap seal ≈ fan static pressure in mm w.g. plus a margin — or the fan pulls the seal dry and air-locks the line. Add a cleanout and an air break at discharge.
Drain sizes follow IMC Table 307.2.2; local codes (ASHRAE, UPC) and the equipment maker's pan-outlet size govern the final selection.
Frequently Asked Questions
Related Calculators
🧮 110 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →