ℹ️ About This Calculator
A cooling coil pulls moisture out of the air, and that condensate has to leave the drain pan reliably. Undersized or flat drain lines back water into the pan, which overflows into ceilings and grows microbial slime. This calculator gives the condensate flow rate from cooling capacity, the drain pipe size per IMC Table 307.2.2, and the fall required at your chosen slope.
Condensate rate is driven by latent load, not just tonnage - a humid coastal AHU can shed three times the water of the same unit in a dry climate, which is why the humidity factor matters. Beyond size and slope, two things cause most drain failures: no P-trap (or the wrong trap depth) on a draw-through unit, and no air break or vent, which makes the line airlock and drain in slugs. Always trap the pan outlet, slope continuously at 1% or more, and provide a cleanout - condensate lines block with biofilm more often than any other pipe in the building.
📐 Condensate Flow & Drain Size (ASHRAE / IMC 307)
ASHRAE / IMC 307
Condensate flow: Q (L/hr) ≈ TR × humidity factor × 1.2 humidity factor: dry 0.5 | moderate 1.0 | humid/coastal 1.5 Drain pipe size (IMC Table 307.2.2, by equipment capacity): up to 3 TR -> 20 mm (3/4") 4 - 20 TR -> 25 mm (1") 21 - 90 TR -> 32 mm (1-1/4") 91 - 125 TR -> 40 mm (1-1/2") 126- 250 TR -> 50 mm (2") Slope: Minimum 1% (approx 10 mm fall per metre) Fall per 10 m = slope% × 100 mm
❓ Frequently Asked Questions
🔗 Related Calculators
🧮 99 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/NBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →