How to Size a Generator (kVA): Running Load vs Motor Starting Surge

26 Jul 2026 MEPMate Team 5 views
All Blog Posts
Table of Contents
    How to Size a Generator (kVA): Running Load vs Motor Starting Surge

    Quick answer: Size a generator for two things — the steady running load (sum the kW, divide by power factor to get kVA) and the motor-starting surge, which can be 6–7× the motor's running kVA on a direct-on-line start. Add ~25% margin. The starting surge, not the running load, is what usually decides the set size. Do it in seconds with the generator sizing calculator.

    The mistake: sizing on running load alone

    Add up the kW, convert to kVA, pick the next standard set — done? Then the biggest motor starts, the genset voltage sags, contactors drop out and the set trips on under-frequency. The genset passed the running test and failed the starting test. Every real generator sizing has to survive the worst single motor start with the rest of the load already connected.

    Step 1 — running load (kVA)

    Running kVA = Σ running kW / power factor
      apply a diversity factor if not everything runs at once
      typical PF 0.8 → kVA = kW / 0.8

    Step 2 — the motor-starting surge

    A motor draws a big inrush at start. How big depends entirely on the starting method:

    StarterStarting currentStarting kVA (× motor kVA)
    Direct-on-line (DOL)6 – 7× FLA~6 – 7×
    Star-Delta2 – 3×~2 – 3×
    Soft starter2 – 4×~2 – 4×
    VFD~1 – 1.5×~1 – 1.5×

    So the starter you choose for the largest motor directly sets how big the generator must be.

    Step 3 — the set must accept the biggest step

    The generator has to absorb the largest starting step while already carrying the running load, without the voltage or frequency dipping beyond the limit for your equipment. In practice that means the genset kVA must comfortably exceed running kVA + the starting contribution of the largest motor, then add margin for the future and for altitude/temperature derating.

    Worked example

    Running load: 50 kW @ PF 0.8 = 62.5 kVA  → +25% = ~78 kVA
    Largest motor: 15 kW, started DOL
      motor running kVA ≈ 20 kVA
      DOL starting kVA ≈ 20 × 6 = 120 kVA (momentary)

    On running load alone a ~80 kVA set looks fine. But the 120 kVA DOL surge would collapse it. Two options:

    • Keep DOL → you need a much larger set (~125 kVA) just to ride the start.
    • Switch the big motor to star-delta or a soft starter → the surge drops to ~40–60 kVA and a ~100 kVA set copes easily.

    The cheaper fix is almost always the softer start, not the bigger generator.

    kW or kVA?

    Generators are rated in kVA (apparent power) and kW (real power); kW = kVA × power factor, usually 0.8. Loads are often quoted in kW, so always convert to kVA before comparing with the genset nameplate.

    FAQ

    What size generator do I need? Enough kVA for the running load plus the largest motor's starting surge, with ~25% margin. Enter your loads into the generator sizing calculator for the number.

    Why does my generator trip when a motor starts? The motor's inrush exceeds the set's transient capacity — either the genset is undersized or the motor needs a softer starter.

    How much margin should I add? Around 25% for load growth, plus derating for high altitude and ambient temperature (both cut a genset's output).

    generator sizing DG set kVA motor starting IS 10000