ℹ️ About This Calculator
A diesel generator (DG set) must be sized to handle both the running load and the starting surge of connected equipment - particularly motors, which draw 5–7 times their rated current at start-up. Undersizing causes voltage dip and frequency drop at start; oversizing wastes fuel and causes "wet stacking" in diesel engines running at low load.
IS 10000 specifies methods of tests for internal combustion engines used in generator sets. For building backup power, a demand factor of 0.7–0.85 is typically applied since not all loads operate simultaneously. Critical facilities (hospitals, data centres) use a higher demand factor of 0.9–1.0. CPCB (Central Pollution Control Board) regulations in India mandate emission norms for DG sets - ensure the selected set meets CPCB norms applicable to your state.
📐 Generator Sizing Method (IS 10000)
IS 10000 / IEEE
Step 1 - Total connected kVA: kVA_total = Σ(kW_load / PF_load) Step 2 - Apply demand factor: kVA_demand = kVA_total × Demand Factor (typically 0.7–0.85) Step 3 - Motor starting kVA check: kVA_start = largest motor kW × starting kVA/kW (6–8× for DOL) Generator must handle: kVA_running + kVA_starting_largest_motor Step 4 - Derate for altitude and temperature: Derate 3% per 300m above 1000m elevation Derate 1% per 5°C above 25°C ambient Step 5 - Add 15–20% spare capacity for future loads
🧮 Worked Example
A commercial building has 150 kW of connected load at 0.85 PF average, including one 30kW fire pump motor (DOL start, 6× starting current). Total connected kVA = 150 / 0.85 ≈ 176.5 kVA.
Applying a 0.8 demand factor: 176.5 × 0.8 ≈ 141.2 kVA running load. The largest motor's starting kVA ≈ 30 × 6 / 0.85 ≈ 211.8 kVA (transient, not additive to full running load but must not dip generator voltage below acceptable limits) - typically sized as running load + roughly 40-50% of the largest motor's starting kVA for a DOL start: 141.2 + 0.45×211.8 ≈ 236 kVA. Adding 20% spare capacity: 236 × 1.2 ≈ 283 kVA → select a 320 kVA (256 kW) generator, the nearest standard rating above requirement.
❓ Frequently Asked Questions
🔗 Related Calculators
🧮 110 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/NBC/ASHRAE compliant, free PDF export.