ℹ️ About This Calculator
A chiller is the heart of a central HVAC system - it produces chilled water that is distributed to AHUs and fan coil units throughout the building. Selecting the correct chiller tonnage is critical: undersizing means the building cannot be cooled; oversizing means the chiller cycles on and off, reducing efficiency and increasing maintenance costs. 1 TR (ton of refrigeration) = 3.517 kW of cooling.
AHRI Standard 550/590 governs chiller rating conditions. Air-cooled chillers are rated at 35°C ambient; water-cooled at 29°C entering condenser water. IPLV (Integrated Part Load Value) is the weighted average efficiency over a full operating season - more important than full-load efficiency for Indian buildings where the chiller runs at part load for most of the year. BEE (Bureau of Energy Efficiency) star ratings for chillers are based on IPLV.
📐 Chiller Sizing Formula
ASHRAE / AHRI
Cooling Capacity:
TR = Total Cooling Load (kW) / 3.517
or
TR = Total Cooling Load (BTU/hr) / 12,000
Chiller kW Input:
kW_input = TR × 3.517 / COP
Typical COP: Air-cooled: 2.8–3.5 | Water-cooled: 4.5–6.5
Chilled Water Flow:
Q_chw (L/s) = Cooling (kW) / (ρ × Cp × ΔT)
= kW / (4.187 × 5) [for 7/12°C CHW system]
Condenser Water Flow (water-cooled):
Q_cw = (Cooling kW + Compressor kW) / (4.187 × 5) [for 29/34°C CW]
🧮 Worked Example
An office building has a calculated cooling load of 350 kW. Chiller capacity required: TR = 350 / 3.517 ≈ 99.5 TR - select a 100 TR chiller.
For a water-cooled chiller with COP 5.5: Input power = 100 × 3.517 / 5.5 ≈ 64 kW. Chilled water flow at 7/12°C (ΔT = 5°C): Q_chw = 350 / (4.187 × 5) ≈ 16.7 L/s. Condenser water flow: Q_cw = (350 + 64) / (4.187 × 5.5) ≈ 18 L/s - this sizes the condenser pump and cooling tower selection.
❓ Frequently Asked Questions
🔗 Related Calculators
📄 Related Articles
🧮 110 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/NBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →