❄️ HVAC

Free Online Cooling Coil Selection Calculator

Size an AHU cooling coil: face area, face velocity, number of rows and chilled-water flow from cooling load. ASHRAE / AHRI 410 basis. Free online tool, no sign-up.

📐 Standard: ASHRAE / AHRI 410
✅ Free to use
📄 PDF export
📱 Mobile friendly
❄️
Cooling Coil Selection Calculator
Reference: ASHRAE / AHRI 410
❄️ HVAC
Size an AHU cooling coil: face area, face velocity, number of rows and chilled-water flow from cooling load. ASHRAE / AHRI 410 basis. Free online tool, no sign-up.
Inputs
Results

About This Calculator

The cooling coil is the heart of an air handler, where warm air gives up heat to chilled water. This calculator estimates the coil face area, face velocity, number of rows and chilled-water flow from the total cooling load and design conditions, following ASHRAE and AHRI 410 practice.

Face velocity is kept around 2.0-2.5 m/s - higher velocities carry condensate off the coil and increase pressure drop. The number of rows and fin spacing set how much the air is cooled and dehumidified; deeper coils give a lower off-coil temperature but higher air-side resistance. Chilled-water flow follows from the load and the water temperature rise (usually 5-6 °C).

Cooling Coil Formulas

ASHRAE / AHRI 410

Face area = Q_air / V_face
Water flow = load / (4.186 × ΔT_water) Q_air = supply airflow, m³/s
V_face = coil face velocity, m/s (2.0-2.5)
load = coil cooling load, kW
4.186 = water specific heat, kJ/kg·K
ΔT_water = chilled-water temperature rise, °C (5-6)

Worked Example

Example: An AHU handling 2 m³/s of air at a 2.25 m/s face velocity needs a face area of 2 / 2.25 ≈ 0.89 m². For a 35 kW coil load with a 5.5 °C water rise, chilled-water flow = 35 / (4.186 × 5.5) ≈ 1.52 L/s. A 4-6 row coil typically achieves the required off-coil condition for comfort cooling.

Coil Face Velocity & Rows Reference (AHRI 410)

Face velocity and row count are the key selection levers. Guidance:

ParameterTypical rangeEffect
Face velocity2.0 – 2.5 m/sAbove ~2.5 m/s risks condensate carry-over
Rows (comfort cooling)4 – 6More rows = lower off-coil temp, higher ΔP
Fin spacing1.8 – 3.2 mmTighter fins = more capacity, easier fouling
Water temp rise5 – 6 °CLarger rise = lower flow, smaller pipes

Sensible vs Total Load

The coil handles both sensible (temperature) and latent (moisture) load. High-latent applications (kitchens, dense occupancy) need a colder, deeper coil to reach a low enough off-coil dew point. Always select on the total load and the required off-coil condition, not the sensible load alone.

Indicative values - final selection uses the manufacturer's coil-rating software to AHRI 410.

Frequently Asked Questions

How do I select a cooling coil? +
Size the face area from the airflow and a face velocity of about 2.0-2.5 m/s, choose the rows and fin spacing to reach the required off-coil temperature and dew point, then calculate the chilled-water flow from the load and water temperature rise. Confirm with the maker's AHRI 410 rating software.
What face velocity should a cooling coil use? +
About 2.0-2.5 m/s. Below this the coil is oversized; above about 2.5 m/s condensate can be blown off the fins into the ductwork and the air-side pressure drop climbs steeply.
How many rows does a cooling coil need? +
Comfort-cooling coils are typically 4-6 rows. More rows give a lower off-coil temperature and better dehumidification but add air-side pressure drop and fan energy. High-latent loads need deeper coils to reach a low dew point.
How do I calculate chilled water flow for a coil? +
Divide the coil load in kW by (4.186 × water temperature rise in °C). A 35 kW coil with a 5.5 °C rise needs about 1.52 L/s. A larger design rise reduces the flow and pipe size but needs a colder or larger coil.
What is coil bypass factor? +
It is the fraction of air that passes through the coil effectively untreated. A lower bypass factor (deeper coil, tighter fins) gives an off-coil condition closer to the coil surface temperature, improving dehumidification.
Sensible vs total cooling load for coil selection? +
Select the coil on the total load and required off-coil dew point, not the sensible load alone. Latent (moisture) removal needs a colder, deeper coil, so ignoring it under-sizes the coil for humid conditions.
What chilled water temperatures are typical? +
Common design is 7 °C flow and 12-13 °C return, a 5-6 °C rise. Lower flow temperatures improve dehumidification; a larger rise reduces the water flow and pipe sizes but demands a larger or deeper coil.
What standard covers coil ratings? +
AHRI 410 is the North American coil rating standard, used with ASHRAE design guidance. Manufacturers publish coil performance to AHRI 410, which their selection software applies to your airflow, water and load conditions.

Related Calculators

🧮 110 Free MEP Calculators

Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.

Browse All Calculators →

⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →