🔌 Electrical

SWA Cable Calculator – Armoured Cable Current Rating, Size & Voltage Drop

Free SWA cable calculator: current-carrying capacity, current rating, size and voltage drop for steel wire armoured (SWA) cables per NEC. Check 1.5, 16, 25, 35, 50 & 95 mm² SWA.

📐 Standard: NEC
✅ Free to use
📄 PDF export
📱 Mobile friendly
🔌
SWA Cable Full Calculator Calculator
Reference: NEC
🔌 Electrical
Free SWA cable calculator: current-carrying capacity, current rating, size and voltage drop for steel wire armoured (SWA) cables per NEC. Check 1.5, 16, 25, 35, 50 & 95 mm² SWA.
Inputs
Results
Calculation confidence: Planning-levelSuitable for early design, estimating and feasibility checks. Verify the final design against the governing code and a licensed engineer before construction or procurement.
Was this helpful?
💬 Suggest an improvement

About This Calculator

This comprehensive SWA cable calculator performs all three checks required for correct cable selection: current-carrying capacity (with derating), voltage drop (per km from cable data), and short-circuit withstand (adiabatic equation). All three must pass — the most onerous determines the final cable size. Per NEC (PVC-insulated) and NEC (XLPE-insulated) armoured cables.

NEC Part 2 (XLPE-insulated steel wire armoured cables) is the preferred specification for new LT power distribution cables in the US. XLPE cables carry approximately 25–30% more current than equivalent PVC cables. Short-circuit rating check is critical for cables near the transformer (high fault levels). All three checks must pass; typically voltage drop governs for long runs, current rating for short runs near the transformer.

Three-Check Cable Sizing Method

NEC

Check 1 – Current Carrying Capacity: I_cable ≥ I_design / (k_temp × k_depth × k_grouping) Check 2 – Voltage Drop: ΔV = I_design × (r cos φ + x sin φ) × L × 2 / 1000 [single-phase] ΔV = I_design × (r cos φ + x sin φ) × L × √3 / 1000 [three-phase] r, x from NEC cable data tables (Ω/km) ΔV% ≤ 5% total (NEC) Check 3 – Short Circuit Rating: I_sc × √t ≤ A × K K = 143 for copper/XLPE; K = 115 for copper/PVC K = 94 for aluminium/XLPE; K = 76 for aluminium/PVC

Worked Example

A 3-phase feeder carries a design current of 180 A over a 120 m run, with a fault current of 15 kA cleared in 0.3 seconds. Check 1: with derating factors (0.9 depth × 0.85 grouping) a 95 mm² XLPE/SWA cable rated 210 A gives an effective capacity of 210 × 0.9 × 0.85 = 161 A, which is insufficient, so 120 mm² (240 A rated, 184 A effective) is chosen. Check 2: at r = 0.196 Ω/km, voltage drop = 180 × 0.196 × 120 × √3/1000 ≈ 7.3 V (1.8%), well within the 5% limit. Check 3: required copper/XLPE area = (15,000 × √0.3)/143 ≈ 57 mm², comfortably less than 120 mm². The 120 mm² cable passes all three checks.

Frequently Asked Questions

Which check most often determines the cable size? +
For short cable runs (under 50 m) near the transformer: short-circuit withstand often governs – small cables cannot withstand the high fault current even for the short time before protection operates. For medium runs (50–200 m): current-carrying capacity usually governs. For long runs (over 200 m): voltage drop usually governs – the cable must be upsized to keep ΔV% within the 5% limit.
What is the protection operating time used in the short-circuit check? +
Use the relay/fuse operating time at the maximum fault current for that cable. For MCCBs and fuses close to the transformer: 0.1–0.4 seconds is typical. For cables with time-delayed protection (backup relay): 1–3 seconds. Shorter operating time allows a smaller cable to pass the short-circuit check. Always use the actual clearing time from the relay coordination study, not a guess.
Can I use a 3-core cable for a 3-phase circuit? +
For a 3-phase circuit with a separate earth conductor: use 3-core cable (phases only) + separate earth. For a 3-phase circuit with neutral and earth combined in the cable: use 3.5-core (3 phases + half-size neutral) or 4-core (3 phases + full neutral), with the armour serving as earth or a separate earth conductor. 4-core cables are standard for most US LV distribution (3 phases + neutral in one cable).
How much space should I allow in cable ducts? +
ASHRAE and NEC guidelines: do not fill ducts more than 40% of cross-sectional area (grouping derating assumed if more cables are added). For a 150 mm × 150 mm duct (22,500 mm²): maximum cable fill = 9,000 mm². Select cables based on their overall diameter and stack no more than the fill limit. Keep 25% spare capacity (empty ducts) for future cables. Separate HV, LV power, and signal cable ducts.
What are the standard SWA cable sizes available in the US? +
Standard conductor sizes per NEC: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300, 400, 500, 630 mm². Voltage rating: 1.1 kV (LT) most common; 3.3 kV and 6.6 kV for HT feeder cables. All SWA cables are available in copper and aluminium conductors. Aluminium conductors are used for 50 mm² and above where weight and cost savings are significant.

Related Calculators

🧮 114 Free MEP Calculators

Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.

Browse All Calculators →

⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →