🌡️ HVAC

HVAC Delta T Calculator (ΔT, Heat Transfer & Flow)

Free HVAC delta T calculator: find temperature difference (ΔT = T1 − T2) and the heat transfer Q = ṁ·cp·ΔT for chilled water, hot water and air systems.

📐 Standard: ASHRAE
✅ Free to use
📄 PDF export
📱 Mobile friendly
🌡️
HVAC Delta T Calculator Calculator
Reference: ASHRAE
🌡️ HVAC
Free HVAC delta T calculator: find temperature difference (ΔT = T1 − T2) and the heat transfer Q = ṁ·cp·ΔT for chilled water, hot water and air systems.
Inputs
Results
Calculation confidence: Planning-levelSuitable for early design, estimating and feasibility checks. Verify the final design against the governing code and a licensed engineer before construction or procurement.
Was this helpful?
💬 Suggest an improvement

About This Calculator

Delta T (ΔT) is the temperature difference between the supply and return of an HVAC fluid — the driver of every heat-transfer calculation. This calculator finds ΔT and the heat transferred using Q = ṁ · cp · ΔT for chilled water, hot water and air.

A larger design ΔT lets a system move the same heat with less flow, cutting pump and fan energy — the basis of low-flow / high-ΔT design. Typical values: chilled water 5–7 K, condenser water 5 K, LPHW heating 10–20 K, and air across a cooling coil 8–12 K.

Delta T Formula

ASHRAE

ΔT = |T₁ − T₂|   |   Heat transfer: Q = ṁ · cp · ΔT   (water cp ≈ 4.186 kJ/kg·K, air cp ≈ 1.005 kJ/kg·K)

Worked Example

Chilled water entering a coil at 12 °C and leaving at 7 °C gives a ΔT of 5 K. At 5 L/s that removes about 104.6 kW (≈29.7 TR).

Delta T Reference & Design Guide

How the HVAC Delta T Calculator Works

The calculator takes the difference between your supply and return temperatures to give ΔT, then multiplies the mass flow (flow rate × fluid density) by the fluid specific heat and ΔT to give the heat transfer in kW, also expressed in tons of refrigeration and BTU/h. Selecting Water or Air switches the specific heat and density used.

Why Delta T Matters

  • Higher design ΔT means lower flow, so smaller pipes, pumps and pump energy.
  • Low ΔT at part load is the classic symptom of oversized flow or fouled coils.
  • Air-side ΔT and water-side ΔT are linked at the coil by the same heat-transfer rate.

Frequently Asked Questions

What is the delta T formula? +
Delta T is simply the difference between two temperatures: ΔT = T₁ − T₂. In HVAC it is the supply-to-return temperature difference, and it links to heat load through Q = ṁ · cp · ΔT, where ṁ is mass flow and cp is the specific heat of the fluid.
How do you find delta T? +
Subtract the leaving (return) temperature from the entering (supply) temperature. For chilled water entering a coil at 12 °C and leaving at 7 °C, ΔT = 5 K. Enter both temperatures above and the calculator returns ΔT and the corresponding heat transfer.
What is a good delta T for chilled water? +
Most chilled-water systems are designed for a ΔT of 5–7 K (commonly 6 K). A persistently low ΔT (known as low delta-T syndrome) means excess flow for the load and wastes pump energy.
How is delta T used to calculate cooling load? +
Multiply the mass flow by the fluid specific heat and by ΔT: Q = ṁ · cp · ΔT. For water at 1 L/s and ΔT of 5 K, Q ≈ 1 × 4.186 × 5 ≈ 20.9 kW.
What is delta T for air across a cooling coil? +
A typical dry-bulb ΔT across a cooling coil is 8–12 K. Air has a much lower density and specific heat than water, so a given ΔT moves far less heat per litre per second of flow.

Related Calculators

🧮 110 Free MEP Calculators

Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.

Browse All Calculators →

⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →